4-20mA Current loop output is a type of electrical signal that is used in a series circuit to provide a robust measurement signal.
The sensor or instrument generating the signal acts like a current source providing a constant current output signal for a given measurement independent of supply voltage or circuit impedance.
Unlike voltage outputs, the current output is the same at any particular point in the circuit and is a relatively high power analogue output which can be used in measurement circuits over long distances.
A typical current output is 4 to 20 mA in a 2 wire configuration, but there are 3 wire configurations which can provide 0 to 20mA or 4 to 20mA current loop output signal with a separate positive supply and output connection.
- Anaerobic digestion methane gas 2bar pressure transmitter
- Water Level Transmitters with 4-20mA Output
- HART® Pressure Transmitters
- 4-20mA Output Pressure Sensors
The current can be converted to voltage output for measurement purposes at any point in the circuit by adding a load resistor in series. The voltage drop across the resistor will then vary proportionally with pressure and current. For example a 250 ohm resistor will produce a 1 to 5 volt output signal with 4-20mA current loop signal.
When connecting up a 4-20mA transmitter to a circuit with a measurement load resistor it is important to ensure that there is sufficient supply voltage available across the transmitter positive and negative supply contacts particularly at full scale output.
4-20 milliamps is used extensively throughout the process control industry and is also being increasingly used for manufacturing, aerospace and automotive applications because of the convenience of 2 wire connections, robustness to RFI, and similar size to other types of output devices .
- Vacuum Pressure Transmitters
- Water Level Transmitters with 4-20mA Output
- Dirty water, sludge & sewerage tank level 400 mbar pressure sensor
- Borewell water level sensor for 100m water height
4-20mA Help
2 wire 4-20ma pressure transmitter wiring configuration
The diagram below below shows a simple wiring configuration for current loop pressure transmitter. It is assumed that the measurement device includes a sufficient load resistance for measuring a current loop. If the measurement device is a multi-meter it is unlikely to include sufficient load resistance, so in this case you will need to include a separate load resistor, e.g. 250Ω added in series to the current loop.
Series or parallel 250Ω resistor to create 1-5Vdc from 4-20mA
If a 4-20mA signal is connected to a DCS circuit that accepts a 1-5 Vdc input, which of these statements are correct?
- Connect 250 Ohms resistor in parallel
- Connect 250 Ohms resistor in series
Either statements can be true because it depends on which part of the circuit you are referring to.
Statement 1 would be true if you were relating the connection of the resistor to the 1-5Vdc signal input – Connect 250 Ohms resistor in parallel with the 1-5Vdc input wires.
Statement 2 would be true if you were relating the connection of the resistor to the current loop circuit – Connect 250 Ohms resistor in series with the 4-20mA current loop circuit.
If you were to ask what is the most usual way of describing how a 4-20mA current loop signal is converted to a 1-5Vdc output signal, then statement 2 would be the one that most people use.
2 & 4 wire comparison
What is difference between a two wire and a four wire 4 to 20 milliamp transmitter?
Two wire 4-20mA transmitter will have a single loop circuit with the transmitter [+/-], power supply [+/-] and signal conditioning unit (SCU) [+/-] all connected together in series.
Four wire 4-20mA transmitter will have a separate output and supply circuit. The transmitter output +/- will be connected to the SCU +/-. The transmitter supply +/- will be connected to the power supply +/-.
Convert 4-20mA to 1-5 volt output
I have a pressure transmitter with an output of 4-20mA / 2 wire. How could I change this current output to a voltage output?
Add a load resistor in series with the current loop and then measure the voltage drop across the load resistor.
For example a 250 ohm resistor will convert a 4-20mA signal to 1 to 5 Vdc.
Also note that you will need to allow for the required additional power supply of 5 volts over the sensor’s minimum supply voltage of 9 Vdc, to allow for the extra load resistance.
Why start from 4mA and not lower
Why do current loop transmitters provide a signal which starts from 4ma and not below this?
4-20mA is normally a 2 wire current loop and in order for the device to operate it needs to consume some of the current to function, and this is provided by the minimum current of 4mA.
Also it is useful to know whether the current output device is functioning, unlike a 0-10Vdc signal for example, a zero mA signal would suggest there is a failure in the current loop circuit at some point.
4mA vs 0mA
Why do current loop transmitters provide a signal which starts from 4ma and not 0mA?
The main reason is that 4-20mA is normally a 2 wire current loop and in order for the device to operate it needs to consume some of the current to function, and this is provided by the minimum current of 4mA.
- Sea Water Resistant Pressure Transmitters
- Natural Gas Pressure Transmitters
- Differential Pressure Transmitters
- 200m deep well pump water level sensor, switch & display
Glossary of Measurement Signal technical terms
- 2 Wire
- 3 Wire
- 4 Wire
- Amplified Voltage Output
- BFSG – Bonded Foil Strain Gauge
- Deadband
- FSO – Full Scale Output
- HART®
- mV/V – Millivolts per Volt Output Signal
- NC – Normally Closed
- NO – Normally Open
- Piezoresistive Strain Gauges
- Ratiometric
- Span
- Span Offset
- Span Sensitivity
- Square Root Extraction
- Threshold
- Totalizer
- Transducer
- Transmitter
- TSL – Terminal Straight Line
- TSS – Thermal Span or Sensitivity Shift
- Turndown Ratio
- USB
- Vented Cable
- Wheatstone Bridge Strain Gauge
- Zero Offset
- Zero Tare
Help from Measurement Signal resources
- How to get a 10 volt signal from a 4-20mA output pressure sensor
- Transforming a 2 wire Current Loop into a Voltage Output Signal
- Supply voltage and load resistance considerations for pressure transmitters
- What can cause random variation in pressure transducer output
- What is the difference between zero offset and zero drift?
- Why use 4-20mA and 3-15 psi rather than 0-20mA & 0-15psi