0…6 mH2O or 0…20 ftH2O liquid level range, 4…20 mA, 0…10 V, or 0…5 V output signal hydrostatic liquid level sensors.
These hydrostatic liquid level sensors will measure from 0 to 6 metres of water column or 0 to 20 feet of water column liquid level ranges, and convert the measured level to a corresponding output signal from 4 to 20 milliamps, 0 to 10 volts, or 0 to 5 volts.
- BMS water tank 6mH2Og range 0-10V out submersible level sensor
- 6 metre range submersible freshwater level transmitter
- Storm water detention tank submersible level transmitter for measuring up to 20ft depth
- Plastic seawater depth probe with 20ft range & 4-20mA out
- Dockside sea water tide level transmitter up to 6 metres depth
- 20 foot deep submersible salt water level transmitter for marine use
- 6m deep ballast tank level transmitter with marine certificate
- 6m range 4-20mA submersible animal feed tank level and PT100 sensor
- IP68 sewage level transmitter for monitoring up to 6 metres depth of waste water
- Landfill level probe for measuring 6 metre depth of leachate
- Cement plant process water basin level sensor
- Dairy farm 6m high milk storage vat 4-20mA level transmitter
- 6m range 4-20mA output water tank level sensor for external fitting
- 0.6 barg range 4-20mA output submersible silicon diaphragm liquid level sensor
- Retention pond 20 feet deep submersible water level sensor
- Depth measurement of surface water flowing to sea
- CIP protected dairy sensor for measuring level of milk in 6m high tank
- Hi-temp level & temperature sensor for 50% NaOH solution
- Hydrostatic level sensor and indicator for frothing oil tank
Calibration Tables
0…6 mH2O to 4…20 mA
Use this table to determine the exact calibration points for a 0…6 metres of water column range to 4…20 milliamps output hydrostatic liquid level sensor. For additional calibration points use our 0…6 mH2O to 4…20 mA converter and enter any value.
% Scale | 0…6mH2O | 4…20mA |
---|---|---|
0 | 0.00 | 4.00 |
10 | 0.60 | 5.60 |
20 | 1.20 | 7.20 |
30 | 1.80 | 8.80 |
40 | 2.40 | 10.40 |
50 | 3.00 | 12.00 |
60 | 3.60 | 13.60 |
70 | 4.20 | 15.20 |
80 | 4.80 | 16.80 |
90 | 5.40 | 18.40 |
100 | 6.00 | 20.00 |
Request product information for a 0...6 mH2O to 4...20 mA hydrostatic liquid level sensor that matches the input and output measurement range from the calibration table above.
0…20 ftH2O to 4…20 mA
Use this table to determine the exact calibration points for a 0…20 feet of water column range to 4…20 milliamps output hydrostatic liquid level sensor. For additional calibration points use our 0…20 ftH2O to 4…20 mA converter and enter any value.
% Scale | 0…20ftH2O | 4…20mA |
---|---|---|
0 | 0.00 | 4.00 |
10 | 2.00 | 5.60 |
20 | 4.00 | 7.20 |
30 | 6.00 | 8.80 |
40 | 8.00 | 10.40 |
50 | 10.00 | 12.00 |
60 | 12.00 | 13.60 |
70 | 14.00 | 15.20 |
80 | 16.00 | 16.80 |
90 | 18.00 | 18.40 |
100 | 20.00 | 20.00 |
Request product information for a 0...20 ftH2O to 4...20 mA hydrostatic liquid level sensor that matches the input and output measurement range from the calibration table above.
0…6 mH2O to 0…10 V
Use this table to determine the exact calibration points for a 0…6 metres of water column range to 0…10 volts output hydrostatic liquid level sensor. For additional calibration points use our 0…6 mH2O to 0…10 V converter and enter any value.
% Scale | 0…6mH2O | 0…10V |
---|---|---|
0 | 0.00 | 0.00 |
10 | 0.60 | 1.00 |
20 | 1.20 | 2.00 |
30 | 1.80 | 3.00 |
40 | 2.40 | 4.00 |
50 | 3.00 | 5.00 |
60 | 3.60 | 6.00 |
70 | 4.20 | 7.00 |
80 | 4.80 | 8.00 |
90 | 5.40 | 9.00 |
100 | 6.00 | 10.00 |
Request product information for a 0...6 mH2O to 0...10 V hydrostatic liquid level sensor that matches the input and output measurement range from the calibration table above.
0…20 ftH2O to 0…10 V
Use this table to determine the exact calibration points for a 0…20 feet of water column range to 0…10 volts output hydrostatic liquid level sensor. For additional calibration points use our 0…20 ftH2O to 0…10 V converter and enter any value.
% Scale | 0…20ftH2O | 0…10V |
---|---|---|
0 | 0.00 | 0.00 |
10 | 2.00 | 1.00 |
20 | 4.00 | 2.00 |
30 | 6.00 | 3.00 |
40 | 8.00 | 4.00 |
50 | 10.00 | 5.00 |
60 | 12.00 | 6.00 |
70 | 14.00 | 7.00 |
80 | 16.00 | 8.00 |
90 | 18.00 | 9.00 |
100 | 20.00 | 10.00 |
Request product information for a 0...20 ftH2O to 0...10 V hydrostatic liquid level sensor that matches the input and output measurement range from the calibration table above.
0…6 mH2O to 0…5 V
Use this table to determine the exact calibration points for a 0…6 metres of water column range to 0…5 volts output hydrostatic liquid level sensor. For additional calibration points use our 0…6 mH2O to 0…5 V converter and enter any value.
% Scale | 0…6mH2O | 0…5V |
---|---|---|
0 | 0.00 | 0.00 |
10 | 0.60 | 0.50 |
20 | 1.20 | 1.00 |
30 | 1.80 | 1.50 |
40 | 2.40 | 2.00 |
50 | 3.00 | 2.50 |
60 | 3.60 | 3.00 |
70 | 4.20 | 3.50 |
80 | 4.80 | 4.00 |
90 | 5.40 | 4.50 |
100 | 6.00 | 5.00 |
Request product information for a 0...6 mH2O to 0...5 V hydrostatic liquid level sensor that matches the input and output measurement range from the calibration table above.
0…20 ftH2O to 0…5 V
Use this table to determine the exact calibration points for a 0…20 feet of water column range to 0…5 volts output hydrostatic liquid level sensor. For additional calibration points use our 0…20 ftH2O to 0…5 V converter and enter any value.
% Scale | 0…20ftH2O | 0…5V |
---|---|---|
0 | 0.00 | 0.00 |
10 | 2.00 | 0.50 |
20 | 4.00 | 1.00 |
30 | 6.00 | 1.50 |
40 | 8.00 | 2.00 |
50 | 10.00 | 2.50 |
60 | 12.00 | 3.00 |
70 | 14.00 | 3.50 |
80 | 16.00 | 4.00 |
90 | 18.00 | 4.50 |
100 | 20.00 | 5.00 |