• Skip to primary navigation
  • Skip to main content
  • Skip to primary sidebar
SensorsONE

SensorsONE

  • Products
  • Contact

Difference between vented and non-vented water level measurement

A hydrostatic level probe typically uses pressure sensor to measure the water level.  The main component of a pressure sensor is the sensing diaphragm which converts the difference in pressure between either side of the diaphragm into a measured signal.

The front of the diaphragm measures the water level pressure (hydrostatic pressure) plus the barometric air pressure pushing down on the water.

Contents

Toggle
  • Vented Level Measurement Device
  • Non-Vented Level Measurement Device
  • Help
    • Plugging the vent line
    • Non-vented sensor in ditches & springs

Vented Level Measurement Device

In a  vented design the back of the diaphragm is exposed to the same barometric air pressure so that it will self-compensate for barometric changes.

  • Pressure on front of diaphragm = Water Depth + Air
  • Pressure on back of diaphragm = Air
  • Actual Measured Pressure = Water Depth

This is the most common way to measure water level with a pressure sensor. There is no need to measure barometric pressure with a device that has a vented pressure reference, which simplifies the installation and reduces the cost because there is less instrumentation required.

Also this method is more accurate because the accuracy of only one sensor is considered, rather than the combination of two measurement devices.

Featured vented reference liquid level measurement products

  • 150cm range 0-10Vdc output bulk milk cooler level sensor with dairy pipe fitting
  • Dam bank narrow diameter submersible level transducer for 30m deep piezometer tubes
  • 16 inch range 4-20mA output submersible shallow water tank level sensor
  • 40m RS485 Modbus RTU submersible borehole pump drawdown depth sensor

Non-Vented Level Measurement Device

A non-vented design has a vacuum sealed on the back of the diaphragm so it does not self-compensate for barometric changes, and has to be compensated by using a separate barometer.
  • Pressure on front of diaphragm = Water Depth + Air
  • Pressure on back of diaphragm = Vacuum
  • Actual Measured Pressure = Water Depth + Air

This method is used less than the vented reference type, but it does have advantages for some applications.

It is not always straightforward to provide a vent path, since the cable maybe terminated underwater, or the air at the surface maybe different to barometric reference pressure.

Vented cables can be problematic if not adequately protected from moisture and humidity, causing calibration shifts, unstable readings and in some cases failure of the sensor.

Featured non-vented reference liquid level measurement products

  • IMCL Submersible Absolute Reference Depth Sensor
  • Detecting water intake blockage on submerged reservoir intake screen using two sensors
  • IMSL IP68 Stainless Steel 316L Hydrostatic Pressure Sensor
  • IMSTL IP68 Water Temperature and Depth Transmitter

Help

Plugging the vent line

Can a vented transducer be converted to an absolute transducer simply by plugging the vent line?

An absolute transducer has a vacuum reference, by plugging the vent line you will instead be trapping in atmospheric pressure, which is called a sealed gauge reference.

You can still use this, but bear in mind that the trapped air pressure will vary if the temperature changes.

Also as the atmospheric pressure changes, so will the level/depth readings by the same amount of pressure change.

These effects on readings will be proportionally greater the lower the pressure range of the device.

Non-vented sensor in ditches & springs

Should we use a non-vented water level sensor in ditches and springs?

We would recommend a vented rather than a non-vented because it allows the sensor to self compensate for changes in barometric pressure. This is particularly important when measuring water level in ditches and springs where the water is much shallower, since the changes in barometric pressure will have a greater impact on the water level reading accuracy if they are not compensated for.

Also the range will need to be much greater for a non-vented type, e.g. a vented (gauge) 3.5 mH2O water level range would need to be a 13.5 mH2O for a non-vented (absolute) range, so the accuracy will be degraded by 4 times before you have even considered the errors associated with barometric changes.

Featured water level measurement products

  • LMP307 Submersible Level Transmitter Water Level Transmitters with 4-20mA Output
  • 200m deep well pump water level sensor, switch & display
  • LMP307 Submersible Level Transmitter
  • 18.605 G Low Cost Submersible Diesel Fuel and Water Tank Level Sensor

Related Help Guides

  • Problem with zero drift when installing submersible pressure sensor
  • Determining water tank volume using hydrostatic pressure

Related Technical Terms

  • Hydrostatic Pressure

Related Online Tools

  • Fluid Depth, Density, Gravity, and Pressure Calculator
  • Well Depth – Water Level Depth to Water Level Height Calculator

Contact us about this Difference between vented and non-vented water level measurement page to request more information, or to discuss your application requirements.

Primary Sidebar

Liquid Level Sensor Specifier

Specify a liquid level sensor

Select your liquid level sensor requirements

Product Enquiry

Send us your enquiry for a product associated with this Difference between vented and non-vented water level measurement page, and get assistance with selecting a product for your application.

Email Your Enquiry

enquiries@sensorsone.com
By clicking "OK" or continuing to use this website you are providing your consent to use cookies as described in our Privacy Policy

© 2026 SensorsONE Ltd, all rights reserved

  • Home
  • Products
  • Tools
  • Legal
  • Contact