The LMK382 submersible level transmitter is a robust solution for wastewater applications in tanks up to 10 feet deep. This hydrostatic sensor is ideal for harsh environments. Position it above the tank bottom to avoid sludge, and consider removing the nose cone to prevent clogging. Connect to your instrumentation via a junction box for easy installation.
The LMK382 submersible level transmitter is a reliable and accurate solution for monitoring wastewater levels in tanks up to 10 feet deep. This hydrostatic level sensor is designed to withstand the harsh conditions often found in wastewater applications, making it an ideal choice for your effluent tank.
To ensure optimal performance and longevity in your wastewater application, consider these installation and maintenance tips:
- Positioning: Mount the LMK382 slightly above the tank’s bottom to prevent contact with settled sludge and minimize the risk of clogging. Suspending it from a point above the tank, as you described, is a common practice for submersible level transmitters.
- Nose Cone Removal: In wastewater environments, removing the protective nose cone can help prevent the build-up of solids around the sensor, which could affect its accuracy. However, this exposes the sensing area to potential damage, so take care during installation and avoid any contact with the sensor.
- Minimizing Disturbance: Position the LMK382 in a location within the tank where water movement and turbulence are minimal. This will help protect the exposed sensing area and ensure consistent readings.
- Junction Box: Connecting the LMK382 to your existing 4-20mA instrumentation via a junction box at the top of the tank is a standard practice that provides a safe and accessible termination point for wiring. Ensure the junction box is appropriately rated for the environment and provides adequate protection for the electrical connections.
The LMK382 is constructed with robust materials to handle the corrosive nature of wastewater. Its design prioritizes long-term stability and minimizes maintenance requirements. By following the installation guidelines and considering the specific characteristics of your wastewater effluent, you can ensure accurate and reliable level monitoring with the LMK382.

LMK382 Waste Water Level Transmitter
- Hydrostatic Pressure Range: 10 ftWG
- Seal gasket material: FKM (standard)
- ATEX or Junction Box Options: ATEX IS approval
- Accuracy: 0.175% FS BSL (standard)
- Mounting Configuration: Submersible with nose cone
- Cable Type: PVC (standard)
- Cable Length (metres): 4